Granular energy demand visibility
DC-LAP-PROD-01 · Site → UPS block → PDU row → Rack · IEC 104 · OPC UA
Real-time
--:--:--
Current Site Draw
1725
kW
of 2000 kW capacity
Peak Demand Today
1940
kW
at 09:40 · 97.0% utilisation
Avg Demand (7-day)
477
kW
23.8% average utilisation
Headroom Now
275
kW
13.8% available
Forecast Load Profile
Forecast model
Loading forecast profile...
Training load
Forecast load
Load Pattern Heatmap — kW intensity by hour & row (24 × 8)
Historian · accumulator delta
00
04
08
12
16
20
ROW-A
ROW-B
ROW-C
ROW-D
ROW-E
ROW-F
ROW-G
ROW-H
Low
High · hover cell to inspect
Power Chain Drilldown · Site → UPS → PDU row → Rack
6-level hierarchy
Site
SITE-DRS-01
1725 kW
86% of 2000 kW
UPS
UPS-A
880 kW
88% of 1000 kW
UPS-B
845 kW
84% of 1000 kW
PDU row
ROW-A
210 kW
88% of 240 kW
ROW-B
195 kW
81% of 240 kW
ROW-C
215 kW
90% of 240 kW
ROW-D
190 kW
79% of 240 kW
ROW-E
200 kW
83% of 240 kW
ROW-F
210 kW
88% of 240 kW
ROW-G
245 kW
88% of 280 kW
Rack
RACK-A1
42 kW
88% of 48 kW
RACK-A2
38 kW
79% of 48 kW
RACK-B1
50 kW
83% of 60 kW
RACK-B2
44 kW
73% of 60 kW
RACK-C1
55 kW
92% of 60 kW
RACK-C2
48 kW
80% of 60 kW
RACK-D1
40 kW
83% of 48 kW
RACK-D2
36 kW
75% of 48 kW
RACK-E1
42 kW
88% of 48 kW
RACK-E2
45 kW
94% of 48 kW
RACK-F1
44 kW
92% of 48 kW
RACK-F2
42 kW
88% of 48 kW
RACK-G1
42 kW
70% of 60 kW
RACK-G2
58 kW
97% of 60 kW
Maximum Demand Trend
15-min avg · kVA
2310
2089
1868
1646
1425
1
5
9
13
17
21
25
29
Daily peak kVA
Contract 2200 kVA
Power Factor Trend — Daily Average
Incomer 1 & 2
1.00
0.96
0.92
0.88
0.84
1
5
9
13
17
21
25
29
Daily avg PF
Target 0.97
Threshold 0.95